PV Fuse and Breaker Sizing Calculator

Three protective devices in a solar system, three different rules. The string fuse is sized from the module's short-circuit current with the 125% factor applied twice; the charge controller output breaker and the inverter DC breaker are ordinary continuous loads with it applied once. Pick the circuit, enter the current as it appears on the datasheet, and get the next NEC 240.6(A) standard size. For a string, enter the raw Isc: the calculator applies both factors itself and checks the result against the module's maximum series fuse rating.

For a PV string this is Isc straight off the module label. For a controller, its rated output current. For an inverter, its DC input current at the low-voltage cutoff.

From the module label. NEC 690.9(B) treats it as a hard ceiling, and the calculator will warn if the result exceeds it.

Enter a circuit current above to see the recommended breaker or fuse size.

Free download

Get the printable solar cable and fuse charts

DC cable ampacity with the ambient and bundling corrections, how far each size runs at 12, 24 and 48 V, PV string fuse sizes from Isc, and battery-to-inverter current by inverter size. Three pages, made to pin by the battery bank.

We store your email with EmailOctopus to send the charts and occasional solar sizing tips, nothing else. Unsubscribe any time. Privacy policy.

How It Works

The string fuse: Isc × 1.25 × 1.25

A PV module is a current source, and its short-circuit current on the label is measured at 1,000 W/m². Real irradiance exceeds that, on a cold clear day with snow on the ground or under the edge of a cloud, so NEC 690.8(A)(1) sets the maximum current of a PV source circuit at 125% of Isc. The circuit then runs at that current for hours at a time, which makes it a continuous load, so NEC 690.8(B) requires the overcurrent device to be rated at 125% of the maximum current. The two factors compound:

String fuse ≥ Isc × 1.25 × 1.25 = Isc × 1.5625

The calculator applies the exact product rather than the rounded 1.56 that trade practice quotes, because rounding down sizes a protective device fractionally low. Enter Isc as the label gives it and nothing else; pre-multiplying by 1.25 yourself would size the fuse 25% too high, and entering Imp instead of Isc would size it too low.

The ceiling on the label: NEC 690.9(B)

Every module label carries a maximum series fuse rating, typically 15 A or 20 A, which is the largest fuse the module's own conductors and bypass diodes can be protected by. NEC 690.9(B) makes it a hard ceiling: the string fuse must not exceed it, and there is no rounding past it. Enter the figure in the optional field and the calculator compares the two. Where Isc × 1.5625 rounds up to a size above the label, the design has to change, not the fuse: a module with a higher rating, or fewer strings in parallel so the back-feed current falls.

When a string needs a fuse at all

A string fuse protects the string from current flowing into it from the other strings when it faults, not from its own output. With one string there is nothing to feed it; with two, a healthy string can push at most its own Isc into a faulted one, which the module's series fuse rating already covers. The requirement bites at three or more strings in parallel, which is where the series vs parallel calculator starts flagging it. Many MPPT controllers carry a single input, so the question is often settled by choosing series over parallel in the first place.

Controller and inverter circuits: continuous loads, applied once

The charge controller's output to the battery and the inverter's DC input are not PV source circuits. They are continuous loads under NEC 210.20(A), and the device is rated at 125% of the circuit current, once. For the controller, the circuit current is its rated output current. For the inverter, it is the DC input current at the inverter's rated output, and at the lowest battery voltage it will run at, because an inverter delivering rated watts draws its highest current when the bank is at its low-voltage cutoff. The inverter sizing calculator reports that figure directly, with the cutoff defaulting to 87.5% of nominal.

NEC 240.6(A) standard sizes

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600

The calculator picks the smallest of these at or above the required rating. Rounding down is never permitted; if the required figure is 17.97 A the answer is 20 A, not 15 A. DC circuits also need a device that is DC-rated at or above the circuit voltage: an AC breaker on a 48 V battery circuit, or a 32 V automotive fuse on a 600 V string, is the wrong part regardless of its amp rating.

Worked examples

A string of modules rated Isc = 11.5 A, maximum series fuse 15 A:

  • Maximum circuit current = 11.5 × 1.25 = 14.375 A (NEC 690.8(A)(1))
  • Required device rating = 11.5 × 1.5625 = 17.97 A (NEC 690.8(B))
  • Next standard size = 20 A
  • 20 A exceeds the 15 A on the label, so the calculator warns under NEC 690.9(B): this module cannot be string-fused at 20 A, and the array needs a module rated 20 A or a layout with no more than two strings in parallel

The DC breaker for a 4,000 W inverter on a 48 V bank, 92% efficiency:

  • DC input at rated output and nominal voltage = 4,000 ÷ (0.92 × 48) = 90.6 A
  • At the 42 V low-voltage cutoff = 4,000 ÷ (0.92 × 42) = 103.5 A, the figure to enter
  • Continuous load: 103.5 × 1.25 = 129.4 A, next standard size 150 A (sizing at nominal would have given 125 A, one size too small)

A 60 A charge controller's output to the battery:

  • Continuous load: 60 × 1.25 = 75 A, next standard size 80 A

In every case the cable on that circuit has to carry the device rating, not just the load: size it with the solar cable size calculator after settling the fuse, not before.

Frequently Asked Questions

Why is a PV string fuse sized at 1.56 times Isc?

Because the 125% factor applies twice. NEC 690.8(A)(1) sets a PV source circuit's maximum current at 125% of the module's short-circuit current, since irradiance in the field can exceed the 1,000 W/m² test condition. NEC 690.8(B) then rates the overcurrent device at 125% of that maximum, because a PV circuit is a continuous load. 1.25 × 1.25 is 1.5625, which the calculator applies exactly; a fuse sized on a single 1.25 from raw Isc is undersized by a fifth.

Do I need a fuse on every solar panel string?

Not with one or two strings in parallel. A string fuse protects a faulted string from the current the healthy strings push back into it, and with only one other string that back-feed cannot exceed a single module's Isc, which its series fuse rating already covers. From three parallel strings the combined back-feed can exceed the module rating, and each string then needs its own fuse. The series vs parallel calculator flags the three-string threshold for you.

What is the maximum series fuse rating on the module label?

The largest fuse the module can be protected by, set by the manufacturer from the ratings of its internal conductors and bypass diodes, and treated by NEC 690.9(B) as a ceiling the string fuse may not exceed. Enter it in the optional field and the calculator checks the result against it. If Isc × 1.5625 rounds up past the label, the fix is a different module or fewer parallel strings, never a bigger fuse.

What size breaker between the battery and the inverter?

Take the inverter's DC input current at its rated output and at the low-voltage cutoff, then apply 125% as a continuous load. A 4,000 W inverter at 92% efficiency on a 48 V bank draws 103.5 A at a 42 V cutoff, so 129.4 A required and a 150 A device; the same inverter on 12 V would draw over 400 A and is the reason 12 V stops at around 2 kW. The device must be DC-rated at or above the bank voltage, and the cable must carry the device rating.

Does the charge controller output need its own breaker?

Yes, between the controller and the battery, sized on the controller's rated output current as a continuous load: a 60 A controller needs 60 × 1.25 = 75 A, so an 80 A device. It protects the cable from the battery, which can deliver thousands of amps into a fault, not from the controller. The PV input side is protected by the string fuses, or by the array's own current limit where there are fewer than three strings.

Embed This Calculator

Add this free calculator to your website. Copy the code below and paste it into your page.